← Industrial electrical products
INDUSTRIAL ELECTRICAL CABINETS
KIOSK station 800 kVA – 35/0.4 kV
1 × 800 kVA · 35/0.4 kV
Outdoor KIOSK station according to HTCO configuration, including station shell, 40.5 kV RMU cabinet, 800 kVA transformer, 1250A low voltage compartment and 300 kVAr compensation cabinet.
Contact for quoteStation enclosure dimensions are tentative. Scope of equipment and measurements provided by Electricity and drawings are confirmed before finalizing the configuration.
Appropriate application
- Power supply for the project uses a 35 kV medium voltage source
- Arrange an outdoor integrated transformer station
Selection characteristics
- The HTCO station shell stands on its own built base
- Configure medium voltage, transformer, low voltage and reactive compensation according to profile
- The size of the station shell is expected, fixed according to the drawing
Quy cách cần đối chiếu trong hồ sơ
| Transformer capacity | 1 × 800 kVA |
|---|---|
| Voltage level | 35/0,4 kV |
| Expected station shell | D3600 × W1800 × H2500 mm |
| Station shell material | Body, wings, roof 2mm corrugated iron; 3mm corrugated iron base; gray electrostatic paint |
| Mounting type | Outdoors, stand on a built-in platform |
| Ventilation | 1 ventilation ball; 2 sets of D300 fans and thermal sensors |
| Station shell auxiliary | MCB Hyundai HGD63N 2P 16A 6kA; 3 sets of lights and limit switches |
| Middle Ages | RMU ABB CCV 3 compartments, 40.5 kV |
| Transformer | VINTEC 800 kVA, 35/0.4 kV, Dyn11, open type, normal ceramic |
| Lower world | Khoang 1250A, MCCB Hyundai HGM1250S 3P |
| Offset resistance | 300 kVAr automatic compensation cabinet |
| Medium voltage cable | Cadisun DATA 1×70, 40.5 kV, configuration 3(1×70) according to documents |
| Cable head | T-plug and cold shrink 35 kV, configuration 3(1×70); The brand latches according to the profile |
| Low voltage cable | Cadisun CXV1×300, 0.6/1 kV; Configuration: 3 fibers/P + 1 fiber/N according to documentation |
| Grounding cable | Cadisun CV1×95 according to configuration |
Be prepared to get the right quote
- Station location and access conditions
- Single line diagram and requirements of Electricity
- Scope of supply, testing and connection
Related categories
Tìm hiểu trước khi yêu cầu báo giá
Reference source of technical information
Thông tin từ hồ sơ cấu hình hoặc media do HTCO cung cấp; model và quy cách đặt hàng cần được xác nhận riêng.
- Configuration in HTCO document dated September 25, 2026